Paxton Access Ltd hereby declares that this product is in conformity with all the essential requirements of Directive
1999/5/EC. This equipment is intended for use in all EU and EFTA countries and all other countries worldwide.
10V DC
14V DC
130 mA
115 kHz 135 kHz
-35 °C
+66 °C
IPX7
45 mm 100 mm
20 mm
85 mm
Voltage
Carrier frequency
Specications
Operating temperature
Electrical
Environment
Dimensions
Min
Max
Width
Height
Depth
Current
Cable length
Read Range
Token
Hands Free Token
Waterproof
Min
Max
Wiring
Connection to a Net2
ACU reader port
+12V DC
Red LED
Amber LED
Green LED
Clock/data1
Data/data0
Not required
0V
Token type and conguration
The reader will recognise 125 kHz HID
TM
proximity tokens in format to produce a Wiegand output (26 to 50 bit) or
EM4100 tokens to produce a Clock and Data output.
The reader scans the rst token presented after power up and will match the reader mode to the format discovered.
If no token is read within 3 minutes of powering up, the reader will default to HID
TM
. If you require EM4100
operation, power cycle the reader and present an EM4100 token within 3 minutes.
Once in HID
TM
or EM4100 mode, the reader will remain in that format.
The declaration of conformity is available on request. Contact details are provided at: http://paxton.info/596
Not Compatible
If used with Net2, the ACU reader port must be congured to read the correct data format.
Where Wiegand cards are used, you must set the correct data format (e.g. Wiegand 26 bits) in the ACU
reader port conguration or create a custom wiegand lter in the Net2 Server Conguration Utility. For further
information see: AN1010 - Conguring custom Wiegand formats < http://paxton.info/990 >
3 metres